Ascon Tecnologic - KxxV - Indicators - ENGINEERING MANUAL -V2.0 PAG. 20
Appendix A
]inp Group - Main and Auxiliary Input Configuration
no. Param. Description
Dec.
Point
Values Default
Vis.
promo
HcFG
Parameter available by serial link
shows the current hardware
0
TC/RTD
TC/PTC
Current
Voltage
Accord-
ing to
HW
Not dis-
played
SEnS
Sensor selection (according to the hw
A4
nTC, Pt100 input
0
J, crAL, S, r, t, ir.J, ir.cA, Pt1, 0... 50 (mV), 0... 60 (mV), 12... 60 (mV) J
TC, PTC, NTC input
J, crAL, S, r, t, Ir.J, Ir.cA, Ptc, ntc, 0... 50 (mV), 0... 60 (mV), 12... 60 (mV)
Ptc
I input 0... 20 (mA), 4... 20 (mA) 4... 20
V input 0... 5 (V), 1... 5 (V), 0... 10 (V), 2... 10 (V), 0... 1 (V) 0... 10
dP Decimal figures 0 0... 3 0
SSc Initial scale readout dP -1999... FSC (E.U.) -1999
FSc Final scale readout dP SSc... 9999 (E.U.) 9999
0.Pot Offset value (to shift the zero readout) 1 SSc... FSc (E.U.) 9999
unit Engineering unit 0 °C o °F 0 = °C
FiL Digital filter on the measured value 1 0 (oFF)... 20.0 (s) 1.0
diF1 Digital input 1 function 0
oFF = No function;
AAC = Alarm Reset;
ASi = Alarm acknowledge (ACK);
HoLd = Hold of the measured value;
r.Pic = Peaks reset;
0.Pot = Start of the 0.Pot procedure;
r.PoP = Start of the 0.Pot procedure and Peaks reset;
t.rHr = Timer Run/Hold/Reset [transition];
t.run = Timer Run [transition];
t.rES = Timer reset [transition];
t.rH = Timer run/hold [Status];
uP.du = Digital inputs in parallel to the
and keys
OFF
A-13
diF2 Digital input 2 function 0 A-14
]Out Group - Output Configuration
no. Param. Description
Dec.
Point
Values Default
Vis.
promo
1 o1F Out 1 function 0
nonE = Output not used.
AL = Alarm output
t.out = Timer output
t.HoF = Tiemer out - OFF in Hold
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
diF.1 = The output repeates the digital input 1 status
diF.2 = The output repeates the digital input 2 status
H.reg A-16
2 o1AL Alarms linked up with out 0
from 0 to 15
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = Alarm 4
+16 = Sensor break (burn out)
AL1 A-17
3 o1Ac Out 1 action 0
dir = Direct action
rEU = Reverse action
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
dir C-0
4 o2F Out 2 function 0
nonE = Output not used.
AL = Alarm output
t.out = Timer output
t.HoF = Tiemer out - OFF in Hold
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
diF.1 = The output repeates the digital input 1 status
diF.2 = The output repeates the digital input 2 status
AL A-19