Manuale XE inglese
Double action regulation "Heat - Cool" (only with Y3 option)
Auxiliary
outputs
Y2 - Y3
(configurable)
Relay
2 contacts NO, 3A/250Vac, 2x10
5
transitions
Action mode
active high (above the set point)
active low (below the set point)
Hysteresis 0,1..10%
Type of Set point
deviation
± 300 digit (with or without
inhibited startup)
band 0..300 digit
independent from beginning to end of scale
Special functions
Loop-Break-Alarm
(signal of control loop defect)
Serial
communication
(option)
Interface 20mA C.L. passive and galvanically isolated
For other data, see manual MIU.-CS/E
Protections
Access to parameters
On three levels for: modification, indication only,
no access
Immunity to disturbances level IV, standard IEC 801-4
All significant data are stored in a non-volatile memory
Single
power
supply
Standard model 100..240V, 48..63Hz, -15% + 10%
Low voltage model 24V, 48..63Hz, -15% + 10% or 24Vdc ± 15%
Absorbed power about 4VA
Auxiliary
power supply
24Vdc ± 10%, 20mA max.
General
features
Isolation group C according to VDE 0110
Climatic group KWF according to DIN 40040
Ambient temperature 0...50°C., humidity 35...85HR%
Protection
Front:IP54 standard (IP65 with Kit AXIP65- 1)
Cover: IP30, terminal board IP20
Material Self-extinguishing UL94V1
Weight about 350 g.
Dimensions 48 x 96, depth 120mm, according to DIN 43700
for 2-wire or 3 or 4-wire transmitter
10 • TECHNICAL DATA