18
Manuale XE inglese
Set point
Main
output Y1
Discontinuous with direct or reverse action
Relay with dual action 2 contacts NO, 3A/250Vac, 2x10
5
transitions
Logic 0.15 Vdc, 20mA max. (for static relays) galvanically isolated
Maximum output 10..100% (1st channel ) -10.. -100% (2nd channel )
Accuracy
(a25°C amb.)
0.2% ± 1 digit (for input with RTD Pt100 and thermocouples)
0.1% ± 1 digit (for input in current and voltage)
Process
Variable "X"
(configurable)
RTD Pt100 Pt100 (IEC 751)
With
configurable
scale field
Thermocouples J-K-S-R (IEC 584), L (DIN 43710)
Direct current 4..20mA, 0..20mA, Ri 30Ω
Direct voltage 0..1Vdc, 0..10Vdc, Ri 10KΩ
1 Local
Distinct ascent and descent
gradient slope
0.1...120.0% scale/min. or step gradient
Higher and lower limit from beginning to end of scale
Control
mode
Algorithm PID, PI, PD, P or On - Off
Proportional band (P) 0,5..1000%
Integral action time (I) 0.1..100min., excludable
Derivative action time (D) 0.01..10min., excludable
Cycling time 1..200 sec.
Hysteresis 0.1..10% (for on-off control)
Dead zone 0..10% for dual action (heat-cool) control
Auto - Tune For automatic parameter adjustment (One shot)
10 • TECHNICAL DATA