Technical Specications
1.4 First time start-up :
Note- In order for the unit to heat the pool (or spa), the lter pump must be running so that the
water can circulate through the heat pump. Without this circulation, the heat pump will not
start.
When all connections have been made and checked, the following steps should be followed:
1). Turn on the lter pump. Check for leaks.
2). Turn on the electrical power supply to the unit, then press the ON/OFF key on the electronic
control
panel. The unit should start when the time delay period has elapsed.
3). When the unit has been running for a couple of minutes, check if the air leaving the unit is cooler
than the ambient temp.
4). Check the performance of the ow switch as follows: with the unit running turn the lter pump o.
The unit should also switch o automatically.
5). The unit and the lter pump should run 24 hours a day until the desired pool water temperature has
been reached. Once the set temperature is reached, the unit will switch itself o. As long as the lter
pump is running, the unit will restart automatically when the temperature of the pool water drops more
than 1°C below the set temperature.
Depending on the starting temperature of the pool water and the air temperature, it can take several
days for the water to reach the desired temperature. Covering the pool can drastically reduced this
period.
Water ow switch—the unit is equipped with a ow switch that is switched on when enough water
has owed through the unit and that is switched o when the water ow becomes too low. (E.g. When
the lter pump is switched o).
Time delay— the unit is equipped with a built-in 3-minute start delay included to protect electrical
components and contacts. After this time delay, the unit will automatically be restarted. Even a brief
interruption of the power supply will activate the start delay and prevent the unit from starting imme-
diately. Additional interruptions of the power supply during the delay period will have no eect on the
3-minute countdown.
Model Codes Voltage (volt) Current (A)
Cable diameter (mm
2
)
for max length 20m
EVOLine 6 66069-R32 220-240 4.1 2 x 1.5mm
2
+Ground
EVOLine 10 66070-R32 220-240 6.2 2 x 2.5mm
2
+Ground
EVOLine 13 66071-R32 220-240 8.9 2 x 2.5mm
2
+Ground
EVOLine 15 66072-R32 220-240 9.7 2 x 2.5mm² +Ground
EVOLine 17M 67405-R32 220-240 11 2 x 2.5mm² +Ground
EVOLine 20M 66073-MOD 220-240 15.9 2 x 4.0mm² +Ground
EVOLine 20T 66073-R32 380-400 5.1 4 x 2.5mm
2
+Ground
EVOLine 25M 66074M-MOD 220-240 16.8 2 x 4.0mm² +Ground
EVOLine 25T 66074-R32 380-400 5.6 4 x 2.5mm
2
+Ground
EVOLine 35T 66075-MOD 380-400 10.1 4 x 4.0mm
2
+Ground
For water pump connection, please externally equip suitable A/C contactor (not included in heatpump)