Inst.296 Viron eVo Series Pool & Spa Heater V12.13
11
CLEARANCES
Installation clearances must comply with AS/NZ 5601. The heater is approved for installation at reduced
clearances as below.
Outdoor Clearances from combustible surfaces non combustible surfaces
Front
300mm
300mm
Both sides
300mm
300mm
Rear
300mm
50mm
Above
1000mm
1000mm
Indoor Clearances from combustible surfaces non combustible surfaces
Front
300mm
300mm
Both sides
300mm
50mm
Rear
300mm
50mm
Above
500mm
500mm
Heater must be installed on a fireproof base.
VENTILATION
When installing the heater indoors, it is imperative that an adequate supply of fresh air is provided for combustion.
Failure to provide adequate ventilation voids all warranties and may be a danger to persons or property.
Two permanent openings shall be provided directly to outside. The openings shall be located to ensure the
distance between the top of the upper opening and the ceiling of the room or enclosure, and the distance between
the bottom of the lower opening and the floor of the room or enclosure does not exceed 5% of the height of the
room or enclosure.