PE6108AV / PE6208AV / PE8208AV User Manual
100
Administrator Login Failure
If you are unable to perform an Administrator login (because the Username and
Password information has become corrupted, or you have forgotten it, for
example), you can clear the login information with the following procedure:
1. Power off the eco PDU and remove its housing.
2. Short the jumper labeled J4 (PIN1 and PIN2).
3. Power on the eco PDU.
4. When the 2-digit, 7-segment display shows “00”, power off the switch.
5. Remove the jumper cap from J4.
6. Close the housing and start the eco PDU.
After you start, you can use the default Username and Password to log in.