Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
70 mm² < 184 A < 160 A < 145 A < 131 A < 112 A
95 mm² < 223 A < 194 A < 176 A < 158 A < 136 A
120 mm² < 259 A < 225 A < 205 A < 184 A < 158 A
Installation method F according table B.52.1.
Single-core cables, touching in free air
Clearance to wall not less than one cable diameter
Maximum allowed current in function of the ambient temperature for installation method F
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 110 A < 96 A < 87 A < 78 A < 67 A
35 mm² < 137 A < 119 A < 108 A < 97 A < 84 A
50 mm² < 167 A < 145 A < 132 A < 119 A < 102 A
70 mm² < 216 A < 188 A < 171 A < 153 A < 132 A
95 mm² < 264 A < 230 A < 209 A < 187 A < 161 A
120 mm² < 308 A < 268 A < 243 A < 219 A < 188 A
Calculation method for IEC:
Single supply cables (3 phases + PE - configuration (1)):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables)
Install the prescribed fuse on each cable
Parallel supply cable (2 x 3 phases + PE - configuration (2)):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables) and divide
by 2
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phases + PE as in (3):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables) and divide
by √3
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Fuse size: the recommended maximum fuse size divided by √3 on each cable.
Size of the PE cable:
For supply cables up to 35 mm²: same size as supply cables
For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
Example: I
tot
= 89 A, maximum ambient temperature is 45 °C, recommended fuse = 100 A
Single supply cables (3 phases + PE - configuration (1)):
I = 89 A + 10 % = 89 x 1.1 = 97.9 A
Instruction book
2920 7118 31 133