3.3 Electric cable size
Attention
Local regulations remain applicable if they are stricter than the values proposed below.
The voltage drop must not exceed 5% of the nominal voltage. It may be necessary to use
cables of a larger size than those stated to comply with this requirement.
GX 7 GX 11
Frequency
(Hz)
Voltage
(V)
Cable size Cable size
IEC
(mm
2
) (mm
2
)
50 200 16 (6 XLPE or EPR) 25 (16 XLPE or EPR)
50 230 10 16 (10 XLPE or EPR)
50 400 4 6
50 500 4 6
60 440/460 4 6
60 380 4 6
CSA/UL AWG AWG
60 200 6 6
60 208-230 / 460 8-8 / 10 6-6 / 8
60 575 12 10