2920 1443 01
38
Instruction book
50 Hz 50 Hz 60 Hz 60 Hz
Air dryer type MD400- MD400 W- MD400- MD400 W-
10 10 10 10
Compressor type ZT160 ZR160 ZT160 ZR160
ZT200 ZR200 ZT200 ZR200
Compressed air effective inlet pressure . . . . . . . . . . . . . bar(e) 10.5 10.5 10.5 10.5
Volume flow at dryer inlet 1)
- Minimum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s 372 386 346 360
- Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s 482 500 434 448
Dewpoint of dried compressed air 2)
- Minimum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . °C -25 -25 -25 -27
- Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . °C -30 -30 -30 -30
Temperature of dried compressed air . . . . . . . . . . . . . . . °C 41 41 41 41
Pressure drop over dryer (approx.) 3)
- Minimum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar 0.21 0.21 0.22 0.22
- Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar 0.27 0.27 0.27 0.27
Cooling air flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s 1900 --- 1900 ---
Cooling water consumption (approx.) with temperature
rise of 5°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s --- 0.8 --- 0.8
Max. electric power input . . . . . . . . . . . . . . . . . . . . . . . W 920 120 1344 144
50 Hz 50 Hz 60 Hz 60 Hz
Air dryer type MD600- MD600 W- MD600- MD600 W-
7.5 7.5 7.5 7.5
Compressor type ZT200 ZR200 ZT200 ZR200
ZT250 ZR250 ZT250 ZR250
Compressed air effective inlet pressure . . . . . . . . . . . . . bar(e) 7 7 7 7
Volume flow at dryer inlet 1)
- Minimum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s 557 599 513 513
- Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s 703 718 712 712
Dewpoint of dried compressed air 2)
- Minimum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . °C -25 -25 -25 -28
- Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . °C -30 -30 -30 -30
Temperature of dried compressed air . . . . . . . . . . . . . . . °C 41 41 41 41
Pressure drop over dryer (approx.) 3)
- Minimum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar 0.20 0.21 0.18 0.18
- Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar 0.25 0.25 0.25 0.25
Cooling air flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s 3000 --- 3000 ---
Cooling water consumption (approx.) with temperature
rise of 5°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l/s --- 2 --- 2
Max. electric power input . . . . . . . . . . . . . . . . . . . . . . . W 1220 120 1944 144

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Atlas Copco MD50 and is the answer not in the manual?

Atlas Copco MD50 Specifications

General IconGeneral
BrandAtlas Copco
ModelMD50
CategoryDehumidifier
LanguageEnglish

Related product manuals