- 22 -
Remote start operation
Installation wirings:
– X25.1 & X25.2 to be wired for the remote start switch.
– X25.3 & X25.4 to be wired for the remote contactor (open/
close).
Fail classes
All the activated alarms of the Qc1002™ have their own
pre-defined fail class.
All alarms are enabled according to one of these three
statuses:
– disabled alarm, no supervision of alarm (OFF).
– enabled alarm, supervision of alarm all the time (ON).
– running alarm, only supervision when the machine is
running (RUN).
Stationary Regeneration Procedure
Atlas Copco recommends that the DPF configuration be left in the AUTO mode at all times, however in the event that a stationary or manual regeneration in desired the
following process should be followed.
– Go to the "STATION REGEN" screen. For normal operation this should be in OFF mode.
§ Press the enter button, this function is password protected contact Atlas Copco service department.
§ Use the up or down arrow to change the selection to ON and press the enter button.
– Go to the "DPF" screen. For normal operation this should be in the AUTO mode.
§ Press the enter button
§ Use the up or down arrow to change the selection to ON and press the enter button.
§ This will set the unit up for regeneration, after a few moments the regeneration icon should appear confirming the unit is regenerating.
Upon completion of the stationary/forced regeneration it is highly recommended to reset the unit to automatically regenerate to prevent engine derate & shutdown due to
high soot load. Follow the process below to return the unit to AUTO mode for normal operation.
– Go to the "STATION REGEN" screen. (For normal operation this should be in OFF mode).
§ Press the enter button, this function is password protected contact Atlas Copco service department.
§ Use the up or down arrow to change the selection to OFF and press the enter button.
– Go to the "DPF" screen. For normal operation this should be in the AUTO mode.
§ Press the enter button,
§ Use the up or down arrow to change the selection to AUTO and press the enter button.
§ The unit is now ready for normal operation.