Atmos Multi Series - Safety Discharge Pipe Sizing; Discharge Pipe Sizing Table; Worked Sizing Example

Atmos Multi Series
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
W
orked example
:
The example below is for a G ½ temperature relief
valve with a discharge pipe (D2) having 4 No.
22mm elbows and length of 7m from the tundish to
he point of discharge. t
From Table 1
Maximum resistance allowed for a straight length
of 22mm copper discharge pipe (D2) from a G ½
temperature relief valve is: 9.0m.
Subtract the resistance for 4 No. 22mm elbows at
.8m each =3.2m 0
Therefore the maximum permitted length equates
t
o 5.8m,
which is less than the actual length of 7m.
Therefore calculate the next largest size (28mm) .
Maximum resistance allowed for a straight length
of 28mm-pipe (D2) from a G ½ temperature relief
valve is: 18m.
Subtract the resistance for 4 No. 28mm elbows at
1.0 m each = 4m.
Therefore the maximum permitted length equates to
14m. As the actual length is 7m, a 28mm (D2)
copper pipe will be satisfactory.
ATMOS MULTI Mk 2 version 2004