– Remove filling device from service connection.
– Remove the rest of the leak detection additive from the service
connection, for example with absorbent paper.
– Seal service connection with sealing cap.
– If necessary, clean area around service connection using
cleaning agents.
– Affix sticker next to service connection with the note that leak
detection fluid was added to this refrigerant circuit.
– Start the A/C system.
Note
♦
A/C system must be operated for a minimum of 60 min. so that
the additive distributes itself in the entire refrigerant circuit
(compressor must be running). Depending on the size of the
leak, it may become visible under UV light within that time.
♦
Depending on the size and location of the leak, it can now last
up to several days until enough refrigerant oil with additive
flows out to determine definitely the leaking area.
– Find the leak in the refrigerant circuit with the UV lamp VAS
6196/4. Refer to ⇒ page 150 .
Detecting Leaks On Refrigerant Circuit Using UV Lamp VAS
6196/4
WARNING
Do not look into UV lamp.
Do not direct UV lamp at other people.