3 Function description
The air is be sucked through the suction grid. The air flows through the heat exchanger and will
be lead through the air outlet grille and/or the sockets into the interior room.
The suction grid has the dimensions 113x113 mm.
The air direction can be changed by rotating the air outlet grille by 90°.
4 Operation
A AURORA control panel (accessories) can be used.
5 Installation
Please pay attention to the actual technical supplement to the general terms of sale and the
safety instructions in contact & Info of www.aurora-eos.com.
Please note: max. allowable pressure for flat tube heat exchangers: 2 bar abs.
The Mini can be installed in variable positions. Please pay attention to the air suction grille in
the installed position. The air suction grille shall not be disguised or closed.
For fixing, screws M5 in corresponding lengths can be used in connection with screw anchors
with an inner diameter of M5 (part number 497-900-0004, length 16 mm, to be set into drills
from the outside). The screw length differes according to vehicle. According fixing drills are on
the bottom or can be drilled at marked position on the housing. During setting the drills, please,
make sure that inside components are not damaged.
As an option fixing elements can be supplied by AURORA.
After installation of the Mini the electrical, the water side connection and optional the air
hose
connections have to be set.
Electrical connection for 2-speed versions:
12V: customer pre-fusing 3A necessary
24V:
customer pre-fusing 2A necessary
Attention: cables may not affect the resistor!