Page 10 AC4100-0036 Rev. 19 3/2018
4100ES Network Display Units with SPS Power Supplies for 4120 Network
SKU Voltage/Listing Description Size Supv. Alarm
A100-5111 120 VAC UL
Additional System Power Supply (SPS); 9 A power supply/charger ;
three 3 A Class A/B NACs, one programmable Aux Relay and one 2 A
Aux Power output, expansion slot for City Circuit or Alarm/Supv/Tbl
Relay option; Canadian model has low battery cutout
4 Blocks 175 mA 185 mA
A100-5113 220-240 VAC UL
Additional System Power Supply (SPS); 9 A power supply/charger;
three 3 A Class A/B NACs, one programmable Aux Relay and one 2 A
Aux Power output, expansion slot for City Circuit or Alarm/Supv/Tbl
Relay option; Canadian model has low battery cutout
4 Blocks 175 mA 185 mA
A100-5125 120 VAC UL
Remote Power Supply (RPS); 9 A power supply/charger similar to
SPS except no City Circuits; will accept one A100-6033
4 Blocks 150 mA 185 mA
A100-5127 220/230/240 VAC UL
Remote Power Supply (RPS); 9 A power supply/charger similar
to SPS except no IDNet channel or City Circuits; will accept one
A100-6033
4 Blocks 150 mA 185 mA
A100-5152 12 VDC Power Option, 2 A @ 12 VDC maximum 1 Block 1.5 A maximum
A100-0634 120 VAC
A100-0635 220/230/240 VAC
Power Distribution Module (PDM); select per system voltage; one required per box or cabinet rack
VCC – Additional Options
SKU Description
A100-6034 Door Tamper Switch with built-in addressable IDNet IAM, one per cabinet assembly if required
A100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
A100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
A100-1290 24 Point I/O Module; I Slot (see data sheet AC4100-0032 for details)
A100-1293 Panel Mount Thermal Printhead Printer, supplied with one roll of paper; requires 3 Slots; see AC4100-0032 for details
4190-9803 Replacement Paper for A100-1293 Printer, one roll
A100-6048 VESDA Air Aspiration Interface; 1 Slot module; 132 mA supervisory or alarm, see AC4100-0026 for details
A100-5013* 8 Point Zone / Relay Module
A100-3109* 250 Point IDNet 2 Module
A100-3110* 250 Point IDNet 2+2 Module
A100-3202* 4 DPDT Relays w/feedback, 10 A
A100-3204* 4 DPDT Relays w/feedback, 2 A
A100-3206* 8 SPDT Relays, 3 A
* See data sheet AC4100-0031 for details