4100ES Network Display Units with SPS Power Supplies for 4120 Network
Page 3 AC4100-0036 Rev. 19 3/2018
master controller includes analog values for: battery voltage, charger
voltage and current, actual system voltage and current, and individual
NAC currents
Low battery cutout is selectable for each SPS power supply, Canadian
models are shipped selected, other models are shipped unselected is
selectable for detector reset, door holder, or coded output operation
Outputs are power-limited, except for the battery charger
2 A auxiliary power output selectable for detector reset, door holder,
or coded output operation
Optional SPS modules (select one)
Optional city connect module (A100-6031, with disc. switches, or
A100-6032, without disc. switches) can be selected for conventional
dual circuit city connections
Optional alarm relay module (A100-6033) provides three C type relays
for alarm, trouble, and supervisory, rated 2 A resistive @ 32 VDC
Packaging Availability
Modules are power-limited (unless specifically noted otherwise)
Enclosure are available for one, two, or three bay sizes or for cabinet
rack mounting
Additional cabinets can be mounted close-nippled for module
expansion
NEMA 1/IP30 boxes, doors with tempered glass inserts, and dress
panels are available in platinum or red (ordered separately)
Cabinet assembly design has been seismic tested and is certified to
IBC and CBC standards as well as to ASCE 7 categories A through F,
requires A100-7912 option for additional legacy card stabilizer brackets
and battery brackets as detailed on data sheet AC2081-0019
Refer to data sheet AC4100-0037 for enclosure details
Software Feature Summary
Selectable service override allows authorized operators to clear alarm
conditions during System Reset even if status has gone to trouble
before reset occurred
Duplicate address error detection
Convenient PC programming using a Microsoft Windows user interface
based program