Digital Counter / Timer / Tach User Manual, 1st Ed.
1-800-633-0405
2-88
Mode N (
n
)
The Total PV increments with each count present value PV.
When the count present value PV counts up to the count
setting value SV both outputs 1 and 2 will turn ON. The count
PV and Total PV will remain at the count SV regardless of
additional input signals.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count present value PV to 0, and
prohibit an input signal from incrementing the count PV. The
trailing edge of the “reset” signal at RST1 enables counting to
begin.
The leading edge of a “reset” input signal at RST2 will reset the
Total PV to 0, and prohibit an input signal from incrementing
the Total PV. The trailing edge of the “reset” signal at RST2
enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
RESET
999999
COUNT SV
COUNT PV
OUT2
OUT1
TOTAL
Input Mode UP
Output Mode N
RST2
RESET
TOTAL PV
0
Mode C (
C
)
The Total PV increments with each count present value PV.
When the count present value PV counts up to the count setting
value SV both outputs 1 and 2 will turn ON momentarily for
the time set in the output pulse width parameter (
tout2
) and
the count PV will reset automatically to 0.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count present value PV to 0, and
prohibit an input signal from incrementing the count PV. The
trailing edge of the “reset” signal at RST1 enables counting to
begin.
The leading edge of a “reset” input signal at RST2 will reset the
Total PV to 0, and prohibit an input signal from incrementing
the Total PV. The trailing edge of the “reset” signal at RST2
enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.