Digital Counter / Timer / Tach User Manual, 1st Ed.
2-103
www.automationdirect.com
Total Counting (
totAL
)
A single count setting value SV is available in Total Counting. Both Outputs 1 and 2 operate concurrently and will
turn ON momentarily for the time set in the output pulse width parameter (
tout2
) or will be maintained ON
depending on the Output Mode selected.
CTT Counter Functions
Total Counting (total)
Counting Up / Counting Down (Ud b)
Counting Up / Counting Down (
Ud B
)
Each leading edge of the input signal at CP1 will increment the count present value PV by 1.
Input Mode:
Mode F (
F
)
The Total PV increments with each increment of the count
present value PV and decrements with each decrement of the
count PV. When the count present value PV counts up to the
count setting value SV both outputs 1 and 2 will turn ON. The
count PV will continue to increment or decrement with each
input signal.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count present value PV to 0, and
prohibit an input signal from incrementing or decrementing
the count PV. The trailing edge of the “reset” signal at RST1
enables counting to begin.
The leading edge of a “reset” input signal at RST2 will reset the
Total PV to 0, and prohibit an input signal from incrementing
or decrementing the Total PV. The trailing edge of the “reset”
signal at RST2 enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
Output Modes:
Each leading edge of the input signal at CP2 will decrement the count present value PV by 1.
TOTAL
Input Mode UdB
OUT2
OUT1
999999
RESET
COUNT SV
COUNT PV
RST2
RESET
TOTAL PV
0
Counting up/down