Digital Counter / Timer / Tach User Manual, 1st Ed.
2-29
www.automationdirect.com
Mode N (
n
)
When the count present value PV counts up to the count
setting value SV1, Output 1 will turn ON momentarily for the
time set in the output pulse width parameter (
tout1
) or will be
maintained ON if the output pulse width parameter (
tout1
) is
set to 0.00. When the count PV counts up to the count setting
value SV2, Output 2 will turn ON. The count PV will remain
at the count SV2 regardless of additional input signals.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count PV to 0, and prohibit an
input signal from incrementing the count PV. The trailing edge
of the “reset” signal at RST1 enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8
RESET
999999
SV2
SV1
PV
OUT2
OUT1
T1 T1
Stage 2
Input Mode UP
Output Mode N
Note: T1 momentary ON time set in output
pulse parameter (tout1), setting tout1=0.00
results in output 1 maintained ON.
0
Mode C (
C
)
When the count present value PV counts up to the count
setting value SV1, Output 1 will turn ON momentarily for the
time set in the output pulse width parameter (
tout1
) or will be
maintained ON if the output pulse width parameter (
tout1
) is
set to 0.00. When the count PV counts up to the count setting
value SV2, Output 2 will turn ON momentarily for the time set
in the output pulse width parameter (
tout2
) and the count PV
will reset automatically to 0. If Output 1 is ON when Output
2 turns OFF, Output 1 will also turn OFF.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count PV to 0 and prohibit an
input signal from incrementing the count PV. The trailing edge
of the “reset” signal at RST1 enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
0
Mode R (
r
)
When the count present value PV counts up to the count
setting value SV1, Output 1 will turn ON momentarily for the
time set in the output pulse width parameter (
tout1
) or will be
maintained ON if the output pulse width parameter (
tout1
) is
set to 0.00. When the count PV counts up to the count setting
value SV2, Output 2 will turn ON momentarily for the time set
in the output pulse width parameter (
tout2
). The count PV is
prohibited from incrementing until the end of the output pulse
time (
tout2
) when both outputs turn OFF and the count PV
is reset automatically to 0.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count PV to 0 and prohibit an
input signal from incrementing the count PV. The trailing edge
of the “reset” signal at RST1 enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.