Digital Counter / Timer / Tach User Manual, 1st Ed.
2-31
www.automationdirect.com
Outputs
Load
Load
OUT1
NPN/
SINKING
OUT2
SPDT
Load
OUT1
SPST
0V CP1
CP2/
GATE (Pause)
+12V RST1
RST2/
START
CP2
Input
CP1
Input
Reset
0V CP1
+12V RST1
RST2/
START
Reset
0V CP1
+12V RST1
RST2/
START
Reset
PNP
INPUTS
L-
Load
OUT2
NPN/
SINKING
Load
0V CP1
+12V RST1
RST2/
START
Reset
L-
L+
NPN
INPUTS
CP1
Input
CP2
Input
CP2
Input
CP1
Input
CP1
Input
CP2
Input
L+
+VDC 0VDC
Externally Powered
Internally Powered
+VDC 0VDC
Externally Powered
Internally Powered
(Optional)
(Optional)
(Optional)
(Optional)
+VDC
0VDC
+VDC
0VDC
10
9
321
15
14
10
15
876
1312
11
876
131211
876
131211
321
876
131211
Counter Wiring Examples
CP2/
GATE (Pause)
CP2/
GATE (Pause)
CP2/
GATE (Pause)
Mode Q (
q
)
When the count present value PV counts up to the count
setting value SV1, Output 1 will turn ON momentarily for the
time set in the output pulse width parameter (
tout1
) or will be
maintained ON if the output pulse width parameter (
tout1
) is
set to 0.00. When the count PV counts up to the count setting
value SV2, Output 2 will turn ON momentarily for the time set
in the output pulse width parameter (
tout2
). The count PV
will continue to increment with each input signal until the end
of the output pulse time (
tout2
) when both outputs turn OFF
and the count PV is reset automatically to 0.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count PV to 0 and prohibit an
input signal from incrementing the count PV. The trailing edge
of the “reset” signal at RST1 enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
RESET
999999
SV2
SV1
PV
OUT2
OUT1
T1T1
T2
T2
Stage 2
Input Mode UP
Output Mode Q
Note: T1 momentary ON time set in output
pulse parameter (tout1), setting tout1=0.00
results in output 1 maintained ON.
T2 = Momentary ON time set in output pulse
0
Mode A (
A
)
When the count present value PV counts up to the count
setting value SV1, Output 1 will turn ON momentarily for the
time set in the output pulse width parameter (
tout1
) or will be
maintained ON if the output pulse width parameter (
tout1
) is
set to 0.00. When the count PV counts up to the count setting
value SV2, Output 2 will turn ON momentarily for the time
set in the output pulse width parameter (tout2). The count
PV will remain at the count SV2 regardless of additional input
signals.
The leading edge of a “reset” signal at RST1 will turn OFF
both outputs, reset the count PV to 0 and prohibit an input
signal from incrementing the count PV. The trailing edge of the
“reset” signal at RST1 enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
RESET
999999
SV1
SV2
PV
OUT2
OUT1
T1
T1
T2
T2
Stage 2
Input Mode UP
Output Mode A
Note: T1 momentary ON time set in output
pulse parameter (tout1), setting tout1=0.00
results in output 1 maintained ON.
T2 = Momentary ON time set in output pulse
0