EasyManua.ls Logo

Automation Direct CTT-1C-D24 - Page 52

Automation Direct CTT-1C-D24
260 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital Counter / Timer / Tach User Manual, 1st Ed.
2-39
www.automationdirect.com
Mode N (
n
)
When the count present value PV counts up or counts down to
the count setting value SV1, Output 1 will turn ON momen-
tarily for the time set in the output pulse width parameter
(
tout1
) or will be maintained ON if the output pulse width
parameter (
tout1
) is set to 0.00. When the count PV counts
up to the count SV2, Output 2 will turn ON. The count PV
will remain at the count SV2 regardless of additional input
signals.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count PV to 0, and prohibit an
input signal from incrementing or decrementing the count PV.
The trailing edge of the “reset” signal at RST1 enables counting
to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8
T1 T1T1 T1
RESET
999999
SV2
SV1
PV
OUT2
OUT1
Stage 2
Input Mode UdA
Output Mode N
Note: T1 momentary ON time set in output
pulse parameter (tout1), setting tout1=0.00
results in output 1 maintained ON.
0
Mode C (
C
)
When the count present value PV counts up or counts down to
the count setting value SV1, Output 1 will turn ON momen-
tarily for the time set in the output pulse width parameter
(
tout1
) or will be maintained ON if the output pulse width
parameter (
tout1
) is set to 0.00. When the count PV counts
up to the count SV2, Output 2 will turn ON momentarily for
the time set in the output pulse width parameter (tout2) and
the count PV will reset automatically to 0. If Output 1 is ON
when Output 2 turns OFF, Output 1 will also turn OFF.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count PV to 0 and prohibit an
input signal from incrementing or decrementing the count PV.
The trailing edge of the “reset” signal at RST1 enables counting
to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
T1T1 T1T1 T1
T1
RESET
999999
SV2
PV
OUT2
OUT1
SV1
T2
T2
Stage 2
Input Mode UdA
Output Mode C
Note: T1 momentary ON time set in output
pulse parameter (tout1), setting tout1=0.00
results in output 1 maintained ON.
T2 = Momentary ON time set in output pulse
parameter (tout2).
0
Mode R (
r
)
When the count present value PV counts up or counts down to
the count setting value SV1, Output 1 will turn ON momen-
tarily for the time set in the output pulse width parameter
(
tout1
) or will be maintained ON if the output pulse width
parameter (
tout1
) is set to 0.00. When the count PV counts
up to the count SV2, Output 2 will turn ON momentarily for
the time set in the output pulse width parameter (
tout2
). The
count PV is prohibited from incrementing or decrementing
until the end of the output pulse time (
tout2
) when both
outputs turn OFF and the count PV is reset automatically to 0.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count PV to 0 and prohibit an
input signal from incrementing or decrementing the count PV.
The trailing edge of the “reset” signal at RST1 enables counting
to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
T1 T1T1 T1 T1 T1
T2
T2
RESET
999999
SV2
SV1
PV
OUT2
OUT1
Stage 2
Input Mode UdA
Output Mode R
Note: T1 momentary ON time set in output
pulse parameter (tout1), setting tout1=0.00
results in output 1 maintained ON.
T2 = Momentary ON time set in output pulse
parameter (tout2).
0