Digital Counter / Timer / Tach User Manual, 1st Ed.
2-59
www.automationdirect.com
Batch Counting (
bAtCH
)
In Batch Counting, count setting value SV controls Output 2 which will turn ON momentarily for the time set in
the output pulse width parameter (tout2) or will be maintained ON depending on the output mode selected. Count
setting value BATCH SV controls Output 1which will be maintained ON.
CTT Counter Functions
Batch Counting (batCH)
Counting Up (Up)
Counting Up (
UP
)
With the input signal OFF at input CP2, each leading edge of the
input signal at CP1 will increment the count present value PV by
1. Turning ON the input signal at CP2, will prohibit the input
signal at CP1 from incrementing the PV.
Input Mode:
Mode F (
F
)
When the count present value PV counts up to the count
setting value SV, Output 2 will turn ON and the batch count
present value BATCH PV will increment by one. The count
PV will continue to increment with each input signal.
The leading edge of a “reset” input signal at RST1 will turn
OFF Output 2, reset the count PV to 0, and prohibit an input
signal from incrementing the count PV. The trailing edge of the
“reset” signal at RST1 enables counting to begin.
When the BATCH PV counts up to the BATCH SV, Output
1 will turn ON. The leading edge of a “reset” input signal at
RST2 will turn OFF Output 1, reset the BATCH PV to 0, and
prohibit an input signal from incrementing the BATCH PV.
The trailing edge of the “reset” signal at RST2 enables counting
to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
Output Modes:
With the input signal ON at input CP1, each trailing edge of the
input signal at CP2 will increment the count present value PV by
1. Turning OFF the input signal at CP1, will prohibit the input
signal at CP2 from incrementing the PV.
999999