Digital Counter / Timer / Tach User Manual, 1st Ed.
1-800-633-0405
2-62
Mode Q (
q
)
When the count present value PV counts up to the count setting value SV,
Output 2 will turn ON momentarily for the time set in the output pulse
width parameter (
tout2
) and the batch count present value BATCH
PV will increment by one. The count PV will continue to increment with
each input signal until the end of the output pulse time when Output 2
turns OFF and the count PV is reset automatically to 0.
The leading edge of a “reset” input signal at RST1 will turn OFF Output
2, reset the count PV to 0, and prohibit an input signal from incre-
menting the count PV. The trailing edge of the “reset” signal at RST1
enables counting to begin.
When the BATCH PV counts up to the BATCH SV, Output 1 will turn
ON. The leading edge of a “reset” input signal at RST2 will turn OFF
Output 1, reset the BATCH PV to 0, and prohibit an input signal from
incrementing the BATCH PV. The trailing edge of the “reset” signal
at RST2 enables counting to begin. The “reset” signal minimum pulse
width is set by reset pulse width parameter (
rtSr
) or DIP Switch 8.
TT
BATCH
Input Mode UP
Output Mode Q
RST2
RESET
BATCH PV
OUT1
BATCH SV=2
999999
RST1
RESET
COUNT SV
OUT2
COUNT PV
0
Mode A (
A
)
When the count present value PV counts up to the count setting value SV,
Output 2 will turn ON momentarily for the time set in the output pulse
width parameter (
tout2
) and the batch count present value BATCH
PV will increment by one. The count PV will remain at the count SV
regardless of additional input signals.
The leading edge of a “reset” input signal at RST1 will turn OFF Output
2, reset the count PV to 0, and prohibit an input signal from incre-
menting the count PV. The trailing edge of the “reset” signal at RST1
enables counting to begin.
When the BATCH PV counts up to the BATCH SV, Output 1 will turn
ON. The leading edge of a “reset” input signal at RST2 will turn OFF
Output 1, reset the BATCH PV to 0, and prohibit an input signal from
incrementing the BATCH PV. The trailing edge of the “reset” signal at
RST2 enables counting to begin.
The “reset” signal minimum pulse width is set by reset pulse width
parameter (
rtSr
) or DIP Switch 8.
TT
OUT2
BATCH
Input Mode UP
Output Mode A
RST2
RESET
BATCH PV
OUT1
BATCH SV=2
999999
RST1
RESET
COUNT SV
COUNT PV
0
Outputs
Load
Load
OUT1
NPN/
SINKING
OUT2
SPDT
Load
OUT1
SPST
0V CP1
CP2/
GATE (Pause)
+12V RST1
RST2/
START
CP2
Input
CP1
Input
Reset
0V CP1
+12V RST1
RST2/
START
Reset
0V CP1
+12V RST1
RST2/
START
Reset
PNP
INPUTS
L-
Load
OUT2
NPN/
SINKING
Load
0V CP1
+12V RST1
RST2/
START
Reset
L-
L+
NPN
INPUTS
CP1
Input
CP2
Input
CP2
Input
CP1
Input
CP1
Input
CP2
Input
L+
+VDC 0VDC
Externally Powered
Internally Powered
+VDC 0VDC
Externally Powered
Internally Powered
(Optional)
(Optional)
(Optional)
(Optional)
+VDC
0VDC
+VDC
0VDC
10
9
321
15
14
10
15
876
1312
11
876
131211
876
131211
321
876
131211
Counter Wiring Examples
CP2/
GATE (Pause)
CP2/
GATE (Pause)
CP2/
GATE (Pause)