DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-7
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Parallel Elements
You may also have to join contacts in parallel. The OR instruction allows you to do this. The
following example shows two contacts in parallel and a single output coil. The instructions
would be STR X0, OR X1, followed by OUT Y0.
Quite often, it is necessary to join several groups of series elements in parallel. The Or Store
(ORSTR) instruction allows this operation. The following example shows a simple network
consisting of series elements joined in parallel.
You can also join one or more parallel branches in series. The And Store (ANDSTR) instruction
allows this operation. The following example shows a simple network with contact branches in
series with parallel contacts.
OUT
Y0
X0
END
X2
X3X1
X4
X5
X6
OUT
Y0
X0
END
X1
X2
Direct SOFT32 Example Handheld Mnemonics
STR X0
STR X1
OR X2
ANDSTR
OUT Y0
END
OUT
Y0
X0
END
X2
X1
X3
STR X0
AND X1
STR X2
AND X3
ORSTR
OUT Y0
END
OUT
Y0
X0
END
X1
Direct SOFT32 Example Handheld Mnemonics
STR X0
OR X1
OUT Y0
END
DirectSOFT
DirectSOFT
DirectSOFT
Combination Networks
You can combine the various types of
series and parallel branches to solve
almost any application problem.The
following example shows a simple
combination network.
Joining Series Branches in Parallel