Accumulating Timer Example using Discrete Status Bits
In the following example, a two input timer (accumulating timer) is used with a preset of 3
seconds. The timer discrete status bit (T6) will turn on when the timer has timed for 3 seconds.
Notice, in this example, that the timer times for 1 second, stops for one second, then resumes
timing. The timer will reset when C10 turns on, turning the discrete status bit off and resetting
the timer current value to 0.
Accumulator Timer Example Using Comparative Contacts
In the following example, a single input timer is used with a preset of 4.5 seconds. Comparative
contacts are used to energized Y3, Y4, and Y5 at one second intervals respectively. The
comparative contacts will turn off when the timer is reset.
Handheld Programmer Keystrokes
X1
T6
TMRA T6
K30
C10
Y7
OUT
X1
C10
123456 78
0
01010203040500
Current
Value
T6
Timing Diagram
Direct SOFT32
Seconds
Handheld Programmer Keystrokes (cont)
STR
$
STR
$
SHFT ENT
2
C
1
B
0
A
TMR
N
SHFT
0
A
3
D
0
A
ENT
STR
$
SHFT
MLR
T
ENT
OUT
GX
ENT
0
A
6
G
1
B
1
B
ENT
6
G
Handheld Programmer Keystrokes
TA20 K10
TA21 K1
TA20 K20
Y3
OUT
Y4
OUT
X1
TMRA T20
K45
C10
X1
C10
123456 780
01010203040500
Current
Value
Timing Diagram
Y3
Y4
Y5
T20