DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-58
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Load Double (LDD)
The Load Double instruction is a 32-bit instruction that loads the
value (Aaaa), which is either two consecutive V-memory locations
or an 8 digit constant value, into the accumulator.
NOTE: Two consecutive Load instructions will place the value of the first load instruction onto the
accumulator stack.
In the following example, when X1 is on, the 32-bit value in V2000 and V2001 will be loaded
into the accumulator and output to V2010 and V2011.
Operand Data Type DL06 Range
A
aaa
V-memory V See memory map
Pointer P See memory map
Constant K 0–FFFFFFFF
Discrete Bit Flags Description
SP53 On when the pointer is outside of the available range.
SP70 On anytime the value in the accumulator is negative.
SP76 On when any instruction loads a value of zero into the accumulator.
LDD
A aaa
1
B
ENT
2
C
0
A
0
A
0
A
ENT
2
C
0
A
1
B
0
A
ENT
Handheld Programmer Keystrokes
Direct
SOFT32
LDD
V2000
X1
Load the value in V2000 and
V2001 into the 32 bit
accumulator
OUTD
V2010
Copy the value in the 32 bit
accumulator to V2010 and
V2011
V2010
Acc.
V2000
67396026
5026
V2001
67395026
V2011
67395026
STR
$
SHFT
ANDST
L
3
D
3
D
OUT
GX
SHFT
3
D
DS Used
HPP Used
DirectSOFT