DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-87
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 and V2001 will be loaded into
the accumulator using the Load Double instruction. The value in the accumulator is added
with the value in V2006 and V2007 using the Add Double instruction. The value in the
accumulator is copied to V2010 and V2011 using the Out Double instruction.
ADDD
A aaa
67395026
Handheld Programmer Keystrokes
LDD
V2000
X1
Load the value in V2000 and
V2001 into the accumulator
ADDD
V2006
Add the value in the
accumulator with the value
in V2006 and V2007
OUTD
V2010
Copy the value in the
accumulator to V2010 and
V201
1
V2010
67395026
V2001
87399072
(V2006 and V2007)
(Accumulator)
20004046 +
87399072
Acc.
STR
$
1
B
SHFT
0
A
3
D
3
D
SHFT
ANDST
L
3
D
3
D
3
D
A
ENTSHFT
ENT
2
C
0
A
0
A
ENT
6
G
2
C
0
A
0
A
0
A
ENT
Discrete Bit Flags Description
SP63 On when the result of the instruction causes the value in the accumulator to be zero.
SP66 On when the 16-bit addition instruction results in a carry.
SP67 On when the 32-bit addition instruction results in a carry.
SP70 On anytime the value in the accumulator is negative.
SP75 On when a BCD instruction is executed and a NON–BCD number was encountered.
Operand Data Type DL06Range
A
aaa
V-memory V See memory map
Pointer P See memory map
Constant K 0–99999999
DS Used
HPP Used
DirectSOFT
Add Double (ADDD)
Add Double is a 32-bit instruction that adds the BCD value
in the accumulator with a BCD value (Aaaa), which is either
two consecutive V-memory locations or an 8–digit (max.)
BCD constant. The result resides in the accumulator.