DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-90
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 and V2001 will be loaded
into the accumulator using the Load Double instruction. The value in V2006 and V2007 is
subtracted from the value in the accumulator. The value in the accumulator is copied to V2010
and V2011 using the Out Double instruction.
SUBD
A aaa
Direct SOFT32
Handheld
Programmer Keystrokes
LDD
V2000
X1
Load the value in V2000 and
V2001 into the accumulator
SUBD
V2006
The in V2006 and V2007 is
subtracted from the value in
the accumulator
OUTD
V2010
Copy the value in the
accumulator to V2010 and
V2011
00390899
01063274
0 1 0 6 3 2
7 4
V2010
V2000
V2001
V2011
00390899
672375
ACC.
STR
$
SHFT
SHFT
ANDST
L
3
D
3
D
3
D
OUT
GX
SHFT
3
D
RST
S
ISG
U
1
B
1
B
ENT
2
C
0
A
0
A
ENT
6
G
2
C
0
A
0
A
0
A
ENT
2
C
0
A
1
B
0
A
ENT
SHFT
_
Discrete Bit Flags Description
SP63 On when the result of the instruction causes the value in the accumulator to be zero.
SP64 On when the 16- bit subtraction instruction results in a borrow
SP65 On when the 32-bit subtraction instruction results in a borrow
SP70 On anytime the value in the accumulator is negative.
SP75 On when a BCD instruction is executed and a NON–BCD number was encountered.
Operand Data Type DL06 Range
A
aaa
V-memory V See memory map
Pointer P See memory map
Constant K 0–99999999
DS Used
HPP Used
DirectSOFT
Subtract Double (SUBD)
Subtract Double is a 32-bit instruction that subtracts the BCD value
(Aaaa), which is either two consecutive V-memory locations or an
8-digit (max.) constant, from the BCD value in the accumulator.