DL06 Micro PLC User Manual, 3rd Edition, Rev. E
Chapter 1: Getting Started
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
1-13
Q. Which devices can I connect to the communication ports of the DL06?
A. Port 1: The port is RS-232C, fixed at 9600 baud, odd parity, address 1, and uses the
proprietary K-sequence protocol. The DL06 can also connect to MODBUS RTU and
DirectNET networks as a slave device through port 1. The port communicates with the
following devices:
DV-1000 Data Access Unit, C-more, DirectTouch, LookoutDirect, DSData or Optimation
Operator interface panels
DirectSOFT (running on a personal computer)
• D2-HPP handheld programmer
Other devices which communicate via K-sequence, Directnet, MODBUS RTU protocols should
work with the DL06 Micro PLC. Contact the vendor for details.
A. Port 2: This is a multi-function port. It supports RS-232C, RS422, or RS485, with
selective baud rates (300 - 38,400 bps), address and parity. It also supports the proprietary
K-sequence protocol as well as DirectNet and MODBUS RTU, ASCII In/Out and
non-sequence/print protocols.
Q. Can the DL06 accept 5VDC inputs?
A. No. 5 volts is lower than the DC input ON threshold. However, many TTL logic circuits
can drive the inputs if they are wired as open collector (sinking) inputs. See Chapter 2 for
I/O wiring guidelines.