EasyManua.ls Logo

AUX ANB78FVAMT - 6.2 Wiring Diagram of Indoor Unit and Outdoor Unit

AUX ANB78FVAMT
149 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AUX-DC inverter ARV outdoor unit individual series technical manual
112
6.2 Wiring Diagram of Indoor Unit and Outdoor Unit
Note:
Power line must be properly fixed;
Each outdoor unit must be grounded;
Each indoor unit must be grounded;
Power wire must be thickened when it is overlong.
Wiring Diagram of Modular Outdoor Unit
Recommended Specification for Power Line of Outdoor Unit (stand-alone power supply)
Item
Unit
Type
Power
supply
Sectional
area of power
line (mm
2
)
Rated
current
breaker
(A)
Rated current of
breaker
Leakage current
Operate time
Containing an
area of ground
wire(mm
2
)
Separate
power
ARV-H615/5R1B
380V-415V
3N
50Hz
16
50
30mA,0.1 sec.
16
ARV-H670/5R1B
16
50
30mA, 0.1 sec.
16
ARV-H730/5R1B
25
80
30mA, 0.1 sec.
16
ARV-H785/5R1B
25
80
30mA, 0.1 sec.
16
ARV-H850/5R1B
25
80
30mA, 0.1 sec.
16
ARV-H900/5R1B
25
80
30mA, 0.1 sec.
16
Recommended Specification for Power Line of Indoor Unit (separate power supply from outdoorunit)
Item
Unit
Type
Power supply
Sectional
area of power
line (mm
2
)
Rated current of
over current
breaker (A)
Rated current of breaker
Leakage current
Operate time
Separate
power
<10 A
Single-phase
220-240V/
50Hz
2.5
16
20 A,30mA,0.1 sec.
≥10 A and <15 A
4
20
25A,30mA,0.1 sec.
≥15 A and <22 A
6
32
40 A,30mA,0.1 sec.
≥27 A
10
40
50 A,30mA,0.1 sec.

Table of Contents