12
b.Tube Pitch(a)x Row
Pitch(b)
mm
22×19.05
22×19.05
22×19.05
c.Fin Pitch
mm
1.5
1.5
1.5
d.Fin Material
Hydrophilic
aluminum fin
Hydrophilic
aluminum fin
Hydrophilic
aluminum fin
e.Tube Outside
Dia.And Material
mm
φ7 Inner grooved
φ7 Inner grooved
φ7 Inner grooved
f.Coil Length x Height x
Width
mm
4128×1232×38.1
4128×1232×38.1
4128×1232×38.1
g.Heat Exchanging
Area
m
2
230.62
230.62
230.62
Air Flow Volume
CFM
16471
17647
17647
m
3
/h
28000
30000
30000
Noise Level
dB(A)
≤65
≤65
≤65
Dimension(W×D
×H)
Net
mm
2350×765×1600
2350×765×1600
2350×765×1600
Packing
mm
2410×815×1770
2410×815×1770
2410×815×1770
Weight
Net
kg
500
500
500
Gross
kg
515
515
515
Refrigerant
type/Quantity
Type
R410a
R410a
R410a
Charged Volume
kg
25
25
25
Design Pressure
MPa
4.2
4.2
4.2
Refrigerant
Piping
Liquid Side
mm
φ19.05
φ19.05
φ19.05
Gas Side
mm
φ34.9
φ34.9
φ34.9
Max. Length
m
1000
1000
1000
Max. Height
m
90m
90m
90m
Ambient Temp (Cooling/Heating)
-5~52/-20~27
-5~52/-20~27
-5~52/-20~27
Stuffing Quantity
20/40/40H
Unit
4/8/8
4/8/8
4/8/8
Notes:
1. Cooling Capacity: Indoor temperature 27DB / 19WB; Outdoor temperature:35DB / 24WB;
2. Heating Capacity: Indoor temperature 20DB; Outdoor temperature:7DB / 6WB;
3. Piping Length:Equivalent piping length:5m,level difference:0m;
4. Anechoic chamber conversion value,measured in test room.During actual operation.These values
are normally somewhat higher as a result of ambient conditions ;
5. The above designs and specifications are subject to change of product improvement without prior
notice.