Rack requirements:
A space of 2.8 inches (71.1 centimeters) for each switch in an EIA or IEC standard 19
inch (48.2 centimeter) equipment rack and TIA 23 inch (58.5 centimeter) equipment rack.
Appropriate space to accommodate unit height:
- ERS 5650 models require one rack unit (1.75 inches, 44.45 millimeters)
- ERS 5632 models require 1.5 rack units (2.625 inches, 66.68 millimeters)
- ERS 5698 models require 2 rack units (3.5 inches, 88.90 millimeters)
The rack must be bolted to the floor, and braced if necessary.
The rack must be grounded to the same grounding electrode used by the power service in
the area. The ground path must be permanent and must not exceed 1 ohm of resistance
from the rack to the grounding electrode.
The following figures illustrate installing the switch in a rack.
Figure 1: Front-mounted rack bracket installation
Attach a bracket to each side of the switch.
English
18 Avaya Ethernet Routing Switch 5600 Series Regulatory Information December 2010