Remarks :
(1) When HP stop running in 30 seconds ,water pump will shut off automatically .
(2) LED wire controller can operate the water pump after connected additional cable to the
pump device in the position of “PUMP” terminal accurately .
(3) It is necessary to put an extra 3-phase transfer device for 3 phase water pump
Parameter
Meaning Range
Default
Remarks
0
To set the entering water temp. under cooling mode
8-35 28
Adjustable
1
To set the entering water temp. under heating mode
15-35
28
Adjustable
Entry into defrosting time period
2
30-90MIN
40MIN
3
4
5
6
7
8
9
A
b
C
d
E
F
G
H
Terms of Entry defrosting function
-30 to 0
-7
Terms of Exit defrosting function
2 to 30 20
Time of Exit defrosting
1 to 12MIN
8MIN
Mode : 0 Cool 1 Heat and Cool 2 Heat and cool
+ auxiliary elec. heating 3 Heat
0-3
3 ( Heat)
Mode selection of Electronic expansion valve
0-1
1 (auto)
Superheat for heating target
-15-15
3
Superheat for cooling target
-15-15
10
Manual adjustment steps of electronic expansion valve
18-94 70
Inlet water temperature
-9-99
Exact testing by value
-9-130
Condenser temperature under heating mode
Gas return temperature
Ambient temperature
Condenser temperature under modeCooling
Actual steps of electronic expansion valve
N*5
-9-99
-9-99
-9-99
Exact testing by value
Exact testing by value
Exact testing by value
Exact testing by value
Exact testing by value
n
85-110
100
o
-10-10
7
Low ambient temperature protection
Refrigerant compressor output temperature protection
Refrigerant compressor output temperature