WWW.BALTIMOREAIRCOIL.COM
7
• Cleanthebasinstrainerandre-install.
• Coverthefandischargetokeepoutdirtanddebris.
• Lubricatethefanshaftbearings,motorbase,andmotorbaseadjustingscrew.
• ApplyRUSTVETO
®
tosteelshafts.
• Inspecttheprotectivenishontheunit.Cleanandrenishasrequired.Referto
“CorrosionProtection”onpage 22 formoredetails.
• Lockoutthefanmotorstartingdeviceinthe“OFF”positiontoensurepersonalsafety
incaseoffutureinspectionorservice.
Prolonged Outdoor Storage
Storage Preparation
• Conductthe“ExtendedShutdown”procedureonpage 6iftheunitisinstalled.
• Ensurethecoldwaterbasinisfullydrainedandthedrainisopen.
• Forstoragepriortoinstallation,allcomponentsandaccessories,whichsometimes
shipinsidethetowerandarenotapermanentxtureinthebasin,shouldberemoved
andstoredindoors.
• RemovethedrainplugfromtheoptionalEASYCONNECT
®
PipingArrangement.The
drainshouldremainopenthroughoutprolongedstorageperiod.Retainthedrainplug
forfutureinstallation
• Removeandstorefanbelts(ifsupplied)atroomtemperature.Tagbeltsappropriately
forfutureidentication.
• Applyaweather-resistantlubricantorheavygreasesuchasAnti-Seize(BACPart#
160069)toallexposedthreadedorangedconnectionsandadjustablemotorbase
threadedrod.
• Insertdesiccantbagsintothecontrolpanel(ifsupplied)toabsorbmoisture.Sealthe
controlpanelforstorage.
• Spraycoatelectricalcomponenthousings(ifsupplied)withasuitableprotective
coating,suchasCosmoline
®
Weathershed,andindividuallycoverthemwithplastic
takingcaretoleaveopeningsforfreeaircirculation.
• Inspecttheprotectivenishontheunit.Cleanandrenishasrequired.Referto
“CorrosionProtection”onpage 22formoredetails.
Motor Recommendations
BACstandardmotorsaredesignedforstorageatambienttemperaturesof-20ºFto104ºF
(-28.9ºCto40ºC).Prolongedperiodsofexposureaboveorbelowthesespeciedconditions
coulddegradecomponentsofthemotorandcausemalfunctionorprematurefailure.
• Motorsshouldberemovedandstoredinsidewheneverpossible.Whenindoorstorage
isnotpossiblethemotorsmustbecoveredwithatarpaulin.Donotuseplasticor
plasticlm.Thiscovershouldextendbelowthemotorandbesecured;however,it
shouldnottightlywrapthemotor.Thiswillallowthecaptiveairspacetobreathe,
minimizingformationofcondensation.
• Caremustalsobetakentoprotectthemotorfromoodingorfromharmfulchemical
vapors.
Unit Operation and
Storage
Start-Up Procedure
Start-Up
Extended Shutdown
Prolonged Outdoor Storage
Storage Preparation
Motor Recommendations
ATTENTION: Covering the unit with
a clear plastic tarpaulin during
storage can trap heat inside the
unit and cause damage to the
PVC components. If units must be
covered during storage, an opaque,
reflective tarp should be used.
DANGER: Do not perform any
service on or near the fans, motors
and drives, or inside the unit
without first ensuring that the
fans and pumps are disconnected,
locked out and tagged out.