Loading...
Model Minimum flow
(l/s)
Appr. minimum heat load
(kW)
VXI 9 3.5 7
VXI 18 3.5 15
VXI 27 3.5 20
VXI 36 3.5 30
VXI 50 5.0 45
VXI 70 7.0 60
VXI-C72 7.0 60
VXI 95 8.0 100
VXI-C108 8.0 90
VXI 144 13.0 150
VXI 145 8.0 150
VXI 180 11.0 130
VXI 190 16.0 200
VXI 215 13.0 220
VXI 288 26.0 280
VXI 290 16.0 280
VXI 360 22.0 250
VXI 430 26.0 420