EasyManuals Logo

Baelz Automatic 6490B User Manual

Baelz Automatic 6490B
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
Page 5
Device manual 6490B / 6490B-y / 6590B
W. Bälz & Sohn GmbH & Co. Koepffstraße 5 D-74076 Heilbronn Telefon (07131) 1500-0 Telefax (07131) 1500-21
2. Operating and setting
Operating level:
6490B
Actuator opens
Actuator closes
At the 6590B
symbols and
displays have the
same meaning.
Alarm
Process variable or manipulated
variable Y or modbus commu-
nication display
other phys. units available as
labels
Setpoint display with actual status
display for:
StOP = STOP DI active
CLOS = CLOSE DI active
OPEn = OPEN DI active
tunE = optimisation running
rAMP = Setpoint ramp running
SP_2 = Second setpoint active
If one of these functions is
active, the SP-display is
alternating between the status
display with the highest priority
and the setpoint. StOP has got
the highest priority and SP_2 the
lowest priority.
Operating level
6490B-y:
The 6490B-y is
equipped with an
additional bargraph
display on the right
hand side of the front-
plate, showing the
current manipulated
variable Y.
The bargraph can be
turned off by the
configuration point
Y.SY (see 3.28 Y.SY).
The bargraph displays the
manipulated variable Y in 10%
steps:
0% all bargraph LEDs off
>0% lowest LED on
10% following LED on
...
90% all LEDs on

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baelz Automatic 6490B and is the answer not in the manual?

Baelz Automatic 6490B Specifications

General IconGeneral
BrandBaelz Automatic
Model6490B
CategoryController
LanguageEnglish

Related product manuals