5. Switch the fuse element or the FI circuit breaker on.
6. If the fuse element trips once again, the fault lies in the VARIABOX. Continue with step 7. If
the fuse elements are not tripping, continue with step 9.
7. Close the OTC flap by tapping it slightly. The flap locked securely with the pre-tensioned spring
mechanism.
8. Put the VARIABOX out of operation and notify your supplier immediately.
ð This completes the troubleshooting here.
9. Insert the plug for the load once again. If the fuse elements trip again, then the fault lies in the
load or its supply cable.
10. Close the OTC flap by tapping it slightly. The flap locked securely with the pre-tensioned spring
mechanism.
11. Inform an electrician.
ð This completes the troubleshooting here.