EasyManua.ls Logo

Bard MEGA-TEC W090A - Page 89

Bard MEGA-TEC W090A
159 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 2100-705B
Page 27 of 43
Wall-Mount Unit 1
FIGURE 24
Communication Wiring: Termination at the First Wall-Mount Unit
1. From the controller, extend the shielded cable through a separate
conduit and route to terminal #1 (positive) and terminal #2
(negative) on the upper terminal block next to the wall-mount
control board on the unit control panel.
These connections are polarity-sensitive. Two-wire communication
from control board is prewired to terminal block. Make sure to
match "+" and "-" symbols on the Field Wiring label above the
terminal block.
2. Connect the wires matching the terminal
designations (+/-) of the Field Wiring
label. Leave the drain wire loose.
3. Connect another cable in a similar
fashion (“daisy chain”) to route in
conduit to the second wall-mount unit.
Connect both drain wires with wire nut.
Maximum two wires per terminal.
To Wall-Mount Unit 2
++
From LC6000
Controller
Unit 1
Terminal Block
++
From LC6000
Controller
Unit 1
Terminal Block

Table of Contents

Related product manuals