TABLE 16
Maximum ESP of Operation
Electric Heat Only
Values shown are for units equipped with standard 1"
throwaway lter or 1" washable lter.
Derate ESP by .15 for 2" pleated lters.
Models 240V-1 208V-1 240V-3 208V-3 460V-3
KW Amps BTUH Amps BTUH Amps BTUH Amps BTUH Amps BTUH
5 20.8 17065 18.1 12800
6 14.4 20500 12.5 15360 7.2 20500
9 21.7 30600 18.7 23030 10.8 30700
10 41.6 34130 36.2 25600
15 62.5 51250 54.0 38400 36.2 51200 31.2 38400 18.0 51200
18 43.3 61430 37.4 46060
20 83.2 68260 57.6 51200
TABLE 17
Electric Heat
Model W42AC, W48AC W60AC, W72AC
Outlet FRONT FRONT
Speed High Low High Low
-A0Z
-A05
-A10
-A15
-A20
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.40
-B0Z
-B06
-B09
-B15
-B18
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
-C0Z
-C09
-C15
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50