Basler AVC63-4 User Manual

Basler AVC63-4
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Publication
91668008
90
Revision
A
First Printing: 09/03
Revised: 04/07
Copyright
2007
FOR
ANALOG VOLTAGE
CONTROLLER
Model AVC63-4 (P/N 9166800136)
Model AVC63-4D
(
P/N 916680013
4
)
INTRODUCTION
AVC63-
4 and AVC63-
4D analog voltage controllers regulate
voltage on 50 or 60 hertz brushless generators. The
controllers include frequency compensation, over-excitation
shutdown, solid-state buildup circuitry, and EMI filtering.
AVC63-4 adjustment potentiometers are located on the
terminals and components side of the controller (see Figure
1). AVC63-4D adjustment potentiometers are accessed
through the controller front panel (see Figure 2).
SPECIFICATIONS
Output Power
Maximum Continuous: 4 Adc at 63 Vdc (252 W)
One Minute Forcing: 7 Adc at 100 Vdc (700 W) with
240Vac power input
Exciter Field DC Resistance
15 to 100
Input Power
Range: 190 - 240 Vac, ±10%, single-phase
Frequency: 50/60 Hz, ±10%
Burden: 500 VA
Sensing Input
190 to 240 Vac, single-phase, 50/60 Hz, ±10%, common
with ac power input
Voltage Adjustment Range
171 to 264 Vac
Regulation Accuracy
Better than ±1.0%, no-load to full-load
Response Time
Less than 1.5 cycles for ±5% changes is sensing voltage
EMI Suppression
Internal electromagnetic interference (EMI) filtering
Overexcitation Shutdown
Field voltage shuts down after time delay if exciter field
voltage exceeds 100 Vdc, ±5%. (See Overexcitation
Shutdown for inverse time delay curve and description.)
Voltage Buildup
Automatic voltage buildup occurs for residual generator
voltages as low as 6 Vac.
Power Dissipation
8 W maximum
Temperature
Operating: –40 to 140°F (–40 to 60°C)
Storage: –85 to 185°F (–65 to 85°C)
Vibration
2 to 27 Hz: 1.3 G
27 to 52 Hz: 0.036 inches, double-amplitude
52 to 1000 Hz: 5 G
Shock
Withstands up to 20 G in each of three mutually
perpendicular axes.
Weight
8 oz (220 g) net
Agency Certifi
cation
UL recognized and CSA certified
CONTROLS
AVC63-4 and AVC63-4D controls consist of jumpers and
screwdriver-adjusted potentiometers.
Jumpers
Two jumpers connect to the controller terminals: the Corner
Frequency jumper and the Voltage Adjust Rheostat jumper.
These jumpers are shown in Figure 3.
Corner Frequency Jumper
Analog volta
ge controllers are delivered with the Corner
Frequency Jumper set for 60 hertz operation. This gives a
corner frequency of 55 hertz. For 50 hertz operation and a
corner frequency of 45 hertz, the Corner Frequency jumper
must be moved to the 50 Hz terminal.
Voltage Adjust Rheostat Jumper
Analog voltag
e controllers are delivered with the Voltage
Adjust Rheostat jumper connected across terminals 6 and 7.
This enables adjustment of the generator output voltage
through the controller’s internal Voltage Control potenti-
ometer. Clockwise rotation of the voltage control increases
generator voltage.
If remote adjustment of the generator output is desired, the
Voltage Adjust Rheostat jumper must be replaced with a
user-supplied rheostat. A 1000 ohm, ½-watt rheostat will
provide adequate voltage adjustment range for most
applications. Figure 8 shows the proper remote rheostat
connections.
Potentiometer Controls
AVC63-4 potentiometer controls are located on the
components and terminals side of the controller and are
shown in Figure 1. AVC63-4D potentiometer controls are
accessible through the controller front panel and are shown
in Figure 2.
INPUT POWER/SENSING INPUT
Power for the exciter fiel
d and analog voltage controller is
derived from the generator output. The acceptable power
input range is 171 to 264 Vac and is connected to terminals
3 and 4. Connect wiring as shown in the interconnection
diagram of Figure 8.
EXCITER FIELD POWER CIRCUIT
Controller terminal F+ is connected to the brushless exciter
field positive terminal and controller terminal F– is
connected to the brushless exciter field negative terminal.
CAUTION
The exciter field dc resi
stance must be 15 or
greater and less than 100
.
If the exciter field dc resistance is less than
15 and the
full-load field current does not exceed the maximum
continuous current rating of the controller, a resistor of
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler AVC63-4 and is the answer not in the manual?

Basler AVC63-4 Specifications

General IconGeneral
BrandBasler
ModelAVC63-4
CategoryController
LanguageEnglish

Related product manuals