Commissioning
Mono Power Unit BUM 62, 63, 64 55
Baumüller Nürnberg GmbH 5.94005.12
6.4 Operation
The controller operates the unit (see controller’s manual).
Errors of the motor-end power unit can be resetted by the controller.
Reset of operational faults reported by the supply unit
y Set the reset input at plug X99AB
y Switch off the +24 V power supply
The reset signal effects on the supply unit only, the stored faults in the motor-end power unit are not in-
fluenced.
Settings do not have to be made for the units BUM 62, 63, 64.