EasyManua.ls Logo

Beck 11-15 - General Specifications

Beck 11-15
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80-1100-00, Rev. 03.2
4
Actuator
Power
120 V ac, single-phase, 60 Hz (Standard), 50 Hz (Optional)
208, 240, 380, 415, 480 & 575 V ac, 50 or 60 Hz (Optional)
Allowable Tolerance +10%
-15%
Maximum Current (Amps) by Model*
Voltage (V ac)
Model
Maximum
Power (W)
120 208 240 380 415 480 575
11-15_ / 11-16_ 50 0.45 0.26 0.23 0.14 0.13 0.11 0.09
11-20_ / 11-26_
11-30_ / 11-36_
104 0.88 0.51 0.44 0.28 0.25 0.22 0.18
11-40_ / 11-46_ 400 3.10 1.79 1.55 0.98 0.89 0.78 0.65

Operating Conditions -40° to 85°C (-40° to 185°F)
0 to 100% relative humidity
Demand Signal Options, with
Electronic Signal Receiver (ESR-5)
0–5 mA, 1–5 mA, 4–20 mA, 10–50 mA, 1–5 V dc, -10 to 10 V dc
Demand Signal Span Adj. 50% to 400% of span (except -10 to 10 V dc)
Demand Signal Zero Adj. -100% to +275% of span (except -10 to 10 V dc)
Deadband 0.6% of span (recommended deadband for most applications). Narrower
and wider deadbands are available.
Sensitivity 25% of deadband.
Direct AC Control 120 V ac for 2-position, multi-position or modulating V ac control
Feedback Signal Options, with
Contactless Position Sensor
(CPS-5)
1–5 mA, 4–20 mA, 10–50 mA, 1–5 V dc, 0–16 V dc, -10 to +10 V dc
Output Stability 0.25% of span from 102 to 132 V ac
±0.03% of span/°C for 0 to 50°C, ±0.05% of span/°C for -50° to 85°C
Linearity ±1% of span, max. independent error
Hysteresis
Isolation
Film Potentiometer
Max. Voltage
Wattage
Linearity
Max. Wiper Current
0.25% of span at any point
Max. leakage of 10 µA at 60 V rms, 60 Hz from output to ground
1,000 ohms
40 V
2 W max.
±0.5%
1 mA
GENERAL SPECIFICATIONS