EasyManua.ls Logo

Belimo 22G14-5C - Page 15

Belimo 22G14-5C
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
To verify if monitors are communicating correctly, change setting
no. 56 on one unit. Press until you reach option 56. Press
to switch from 0 to 1, to turn on the network display. Press
and simultaneously to save, then press and hold for a
few seconds to return home. The unit will display each monitor
connected in order of their address. If the unit does not display
the others scrolling by, check the following;
each unit must have a unique address, setting 39, with no
duplicates
end-of-line jumpers are set on units at ends of cable only
polarity of the communication cable and the 24 Vac is the
same on all units
verify wire connections for shorts, and loose wires, etc.
8. To further test communication, press and hold the up button on
a monitor for 5 seconds to start manual mode (5 minutes). This
will close the relay 1 on that unit and all of the other units on the
network. See section 5 to set up a conguration for multiple
zones.
3.3 Installation
Electrical
Distribution
Panel
Magnetic
Starter
Exhaust Fan
Dampers
Fan Power
Source
Power source
for controls
to other
H
S
L
5
6
4
3
2
1
1
Transformer
24 V AC/DC
Monitors