Digital gas monitoring
No. Name Description Range Default
0 AL1 Alarm 1 threshold, activates relay 1 by sensor
1 A1Del Alarm 1 Delay on (seconds) 2-999 30
2 A1Off Alarm 1 Delay off (seconds) 0-999 20
3 AL2 Alarm 2 threshold, activates relay 2 by sensor
4 AL2Del Alarm 2 Delay on (seconds) 2-999 30
5 AL2Off Alarm 2 Delay off (seconds) 0-999 20
6 AL3 Alarm 3 threshold, sounder by sensor
7 A3Del Alarm 3 Delay on (seconds) 2-999 180
8 A3Off Alarm 3 Delay off (seconds) 0-999 20
9 A1Tx Alarm 1 transmit message, CAN
network
0-255
1
10 A1Tx Alarm 1 transmit message, CAN
network
0-255
11 A1Tx Alarm 1 transmit message, CAN
network
0-255
12 A2Tx Alarm 2 transmit message, CAN
network
0-255
2
13 A2Tx Alarm 2 transmit message, CAN
network
0-255
14 A2Tx Alarm 2 transmit message, CAN
network
0-255
15 A3Tx Alarm 3 transmit message, CAN
network
0-255
3
16 A3Tx Alarm 3 transmit message, CAN
network
0-255
17 A3Tx Alarm 3 transmit message, CAN
network
0-255
4.4 List of Settings Sensor A
(upper socket) settings
For UL installation, alarm shall not exceed 200 ppm for CO