O56002 - 04/12 - Subject to change. © Belimo Aircontrols (USA), Inc.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
LCD Electronic Thermostat
EXT-CF230-D202-AF, EXT-CF230-D402-AF
Maintenance mode
When the unit in “OFF” status, press for 5 seconds to enter maintenance mode.
Press “ to change over from disp > 0set > defr > usp > lsp”. If button is not
pressed over 10 seconds, it will return to normal mode automatically.
disp
Display selection - ambient temperature (rt) / setpoint (sp)
In maintenance mode disp”, press , to select rt or sp”.
rt : display ambient temperature (factory setting)
sp : display setpoint
0set
Temperature offset adjustment
In maintenance mode 0set”, press , to adjust ambient
temperature reading.
-3, -2, -1, 0, 1, 2, 3. (factory setting “0”)
defr
Defrost - low temperature protection
In maintenance mode defr”, press , to adjust.
0n = ON
0ff = OFF (factory setting)
usp
Upper set point adjustment (factory setting 35°C)
In maintenance mode usp”, press , to adjust max. temperature
set point.
lsp
Lower set point adjustment (factory setting 35°C)
In maintenance mode lsp”, press , to adjust min. temperature
set point.
do not open
To be opened by accredited servicing agents only Electronic control - Type 2.B
action (micro-disconnection operation). Separate collection for electrical and
electronic equipment.
Wiring Diagrams
230 VAC
EXT-CF230-D202-AF
5 A fuse
On-Off Control - 2 Wires
comm
230 VAC
EXT-CF230-D202-AF
5 A fuse
On-Off Control - 3 Wires
230 VAC
EXT-CF230-D202-AF
5 A fuse
On-Off Control - 2 Wires
Auto Change-Over