EasyManua.ls Logo

Bender COMTRAXX CP9 Series - Page 32

Bender COMTRAXX CP9 Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
32
CP9xx_D00349_08_M_XXEN/02.2022
Modbus TCP
Interface/protocol...................................................................................................................Ethernet/Modbus TCP
Cable length................................................................................................................................................. < 100 m
Operating mode.........................................................................Client for PEM and "third-party devices" assigned
Operating mode........................................Server for access to process image and for Modbus control commands
SNMP
Interface/protocol..............................................................................................................................Ethernet/SNMP
Versions............................................................................................................................................................1, 2c, 3
Supported devices ..................................................................................... query of all devices (channels) possible
Trap support ...........................................................................................................................................................no
Modbus RTU
Interface/protocol.................................................................................................................... RS-485/Modbus RTU
Operating mode...............................................................................................................................................master
Baud rate ....................................................................................................................................... 9.6…57.6 kbit/s
Cable length............................................................................................................................................... < 1200 m
Cable.....................................................................................................shielded, one end of shield connected to PE
recommended ....................................................................................................CAT6/CAT7 min. AWG23
alternative.............................................................................................twisted pair, J-Y (St) Y min. 2x0.8
Connection.................................................................................................... "AMB", "BMB" (see plug-in terminal)
Terminating resistor ..................................120 Ω (0.25 W), can be switched on internally (see plug-in terminal)
Supported Modbus RTU slave addresses .................................................................................................... 2…247
PROFINET
Interface/protocol........................................................................................................................Ethernet/PROFINET
Operating mode............................................................................................................................... slave (IO device)
Digital inputs (1…12)
Number............................................................................................................................................................................. 12
Galvanic separation.........................................................................................................................................................yes
Operating mode ................................................................................selectable for each input: active-high or active-low
Factory setting....................................................................................................................................................active-high
Voltage range (high) ..............................................................................................................................AC/DC 10…30 V
Voltage range (low) .................................................................................................................................... AC/DC 0…2 V
Max. current per channel (at AC/DC 30 V) .................................................................................................................... 8 mA
Connection push-in terminal............................................................................................. (1-1) (2-2) (3-3) … (12-12)
Maximum cable length....................................................................................................................................... < 1000 m
Switching elements
Number...................................................................................................................................................................... 1 relay
Operating mode ................................................................................................................ N/C operation / N/O operation
Function .......................................................................................................................................................programmable
Electrical endurance under rated operating conditions, number of cycles .............................................................10,000
Contact data acc. to IEC 60947-5-1
Utilisation category...............................................................................................................AC-13 / AC-14 / DC-12
Rated operational voltage .............................................................................................................24 V / 24 V / 24 V
Rated operational current....................................................................................................................2 A / 2 A / 2 A
Minimum contact load (relay manufacturer's reference)......................................................................10 μ
A / 10 mV DC
Connection ............................................................................................................................. plug-in terminal (11;12;14)
Buzzer
Buzzer message.............................................................can be acknowledged, adoption of characteristics of new value
Buzzer interval .................................................................................................................................................configurable
Buzzer frequency .............................................................................................................................................configurable
Buzzer repetition ..............................................................................................................................................configurable

Other manuals for Bender COMTRAXX CP9 Series

Related product manuals