12
MYNUTE X R
Menu Parameters
Scrolling message
only if parameter P1.05 = 1
Value
Password
level
Value set
in the factory
Personalised
values
P4.19 WEATHER COMP CURVE
1,0-3,0
AT
0.2-0,8
BT
INSTALLER 2.0
P4.20 NIGHT COMPENSATION 0 / 1 INSTALLER 0
P4.21 CH CLOCK ENABLE 0 / 1 INSTALLER 0
P4.22 MODE SELECTION 0 / 1 INSTALLER 0
P4.23 ZONE1 ENABLE 0 / 1 INSTALLER 0
P4.24 ZONE1 ADDRESS 1 - 6 INSTALLER 1
P4.25
ZONE1 HYDRAULIC
CONFIG
0 / 1 INSTALLER 0
P4.26 ZONE1 TYPE 0 / 1 INSTALLER 0
P4.27 ZONE1 SET
ZONE1 MIN CH SET -
ZONE1 MAX CH SET
USER 40 - 80.5
P4.28 ZONE1 MAX CH SET
AT: ZONE1 MIN CH SET - 80,5
BT: ZONE1 MIN CH SET - 45,0
INSTALLER 80.5
P4.29 ZONE1 MIN CH SET
AT: 40 - ZONE1 MAX CH SET
BT: 20 - ZONE1 MAX CH SET
INSTALLER 40
P4.30 ZONE1 OTR 0 / 1 INSTALLER 0
P4.31 ZONE 1 OTD CURVES
1,0-3,0
AT
0.2-0.8
BT
INSTALLER 2.0
P4.32 ZONE1 NIGHT COMP 0 / 1 INSTALLER 0
P5 DHW
P5.01
ANTI LEGIONELLA
FUCNTION
Only for boiler in
confi guration water tank with
probe (C CASE) (P3.01 = 3)
0 / 1 / 2 INSTALLER 0
P5.02
ANTI LEG. TIME PERIOD
Only for boiler in
confi guration water tank with
probe (C CASE) (P3.01 = 3)
00:00 INSTALLER 03:00 am
P5.03
ANTI LEG. TEMPERATURE
Only for boiler in
confi guration water tank with
probe (C CASE) (P3.01 = 3)
65 ÷ 85 INSTALLER 80
P5.06 TANK FLOW TEMP 65 ÷ 85 INSTALLER 80
P5.07
MODULATING TANK
SUPPLY TEMP
0/1 INSTALLER 0
P5.10 DHW DELAY
NOT AVAILABLE ON THIS MODEL
0
P5.11
DHW ENHANCED
FUNCTION
NOT AVAILABLE ON THIS MODEL
0
P8 CONNECTIVITY
P8.01 BUS 485 CONFIG 0 / 1 / 2 SERVICE 0
P8.03 OT CONFIG 0 / 1 SERVICE 1