Service and Installation Manual
9
2. Parameter list
Menu
Functions
Setting range
HK-01
Freezer
HK-02
Refrigerator
Unit
Common user menu
St
Temperature set value
Upper limitLower limit
-8
36
/
Po
Administrator menu Password
0099password is
55,unmodified
00
00
/
Administrator’s menu
C1
Hysteresis value
0.59.0
7
7
/
120
C2
Compressor start Min. interval
060
3
3
min
C3
Compressor initial start Min. interval
090
0
0
min
C4
Cabinet sensor calibration
-10.010.0
0
0
/
-2020
C5
Temperature set lower limit
-50temperature set value
-10
28
/
-58temperature set value
C6
Temperature set upper limit
temperature set value85
-1
55
/
temperature set value185
C7
Max.standby time after finishing
compressor start Min. interval (note)
090, 0:Max.standby time
calculation is forbidden
9
9
min
C8
Refrigeration Min. running time
090, 0: Refrigeration Min.running
time calculation is forbidden
0
0
min
d1
Evaporator sensor selection
0: Disabled, 1: Enabled
1
0
/
d2
Evaporator sensor calibration
-10.010.0
0
0
/
-2020
d3
Defrost cycle calculation
0: accumulated refrigeration time
1: natural time
1
1
/
d4
Defrost cycle
090, 0: Defrost forbidden
4
4
hour
d5
Defrost status display
0:Display cabinet temperature
1:Display dEF during defrost and
defrost time delay, display cabinet
temperature after finishing defrost
time delay.
2:Always display dEF during defrost
and defrost dripping
3:Always display start-defrost
cabinet temperature during defrost
and defrost dripping
1
1
/
d6
The maximum time of defrost
190
30
30
min
d7
Defrost termination temperature
050
46
46
/
32122
d8
Dripping time after defrost
060, 0: Defrost dripping time
forbidden
0
0
min
d9
Cabinet temperature display time
delay after defrost
090
10
10
min
d10
Time delay after defrost start
060
0:Defrost start time delay is
canceled
0
0
min