Combination
Outdoor air
temp
Indoor air temperature ℃ DB
16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
℃ DB ℃ WB kW kW kW kW kW kW kW kW kW kW kW kW
110%
-19.8 -20.0 47.9 14.02 47.8 14.76 47.7 15.23 47.7 15.64 47.7 16.02 47.5 16.82
-18.8 -19.0 48.4 14.19 48.3 14.82 48.2 15.30 48.2 15.67 48.1 16.13 48.1 16.86
-16.7 -17.0 49.3 14.36 49.2 15.06 49.1 15.40 49.0 15.82 49.1 16.23 48.9 16.94
-13.7 -15.0 50.3 14.53 50.1 15.17 50.1 15.55 50.0 15.90 50.0 16.24 49.9 16.96
-11.8 -13.0 51.1 14.67 51.1 15.22 50.9 15.54 50.9 15.85 50.9 16.27 50.8 16.86
-9.8 -11.0 52.1 14.74 52.0 15.28 51.9 15.53 51.9 15.91 51.8 16.20 51.8 16.77
-9.5 -10.0 52.5 14.72 52.4 15.24 52.3 15.55 52.3 15.83 52.2 16.12 52.2 16.73
-8.5 -9.1 53.0 14.76 52.9 15.27 52.8 15.50 52.8 15.78 52.7 16.13 52.7 16.64
-7.0 -7.6 53.6 14.76 53.6 15.19 53.4 15.42 53.4 15.69 53.4 15.80 53.3 16.51
-5.0 -5.6 55.8 14.97 55.6 15.42 55.6 15.64 55.5 15.90 57.5 15.99 55.4 16.70
-3.0 -3.7 57.9 15.23 57.9 15.62 57.7 15.80 57.7 16.05 62.3 16.31 57.5 16.77
0.0
-0.7 62.5 15.79 62.5 16.17 62.3 16.31 62.3 16.54 64.9 16.80 60.5 16.52
3.0 2.2 67.5 16.32 67.3 16.66 67.3 16.78 67.1 16.99 64.9 16.35 60.5 15.04
5.0 4.1 70.9 16.63 70.9 16.97 69.5 16.59 67.1 15.97 64.9 15.38 60.5 14.15
7.0 6.0 74.5 16.94 73.9 17.05 69.8 15.65 67.1 15.03 64.9 14.46 60.5 13.32
9.0 7.9 78.3 17.21 75.1 16.29 69.9 14.76 67.2 14.16 64.9 13.61 60.5 12.56
11.0 9.8 80.5 16.64 75.1 15.32 69.9 13.90 67.2 13.35 64.9 12.84 60.5 11.85
13.0 11.8 80.5 15.61 75.1 14.38 69.9 13.07 67.2 12.56 64.9 12.08 60.5 11.16
15.0 13.7 80.5 14.71 75.1 13.56 69.9 12.35 67.2 11.86 64.9 11.43 60.5 10.56
18.0 16.8 80.5 13.92 75.1 12.85 69.9 11.27 67.2 11.25 64.9 10.89 60.5 10.06
20.0 18.5 80.5 13.21 75.1 12.22 69.9 10.69 67.2 10.71 64.9 10.44 60.5 9.62
24.0 20.5 80.5 12.61 75.1 11.67 69.9 10.19 67.2 10.26 64.9 10.06 60.5 9.26
100%
-19.8 -20.0 47.6 15.12 47.5 15.79 47.4 16.09 47.3 16.53 47.2 16.85 47.1 17.62
-18.8 -19.0 48.1 15.27 47.9 15.82 47.8 16.18 47.8 16.53 47.7 16.97 47.5 17.59
-16.7 -17.0 49.0 15.37 48.9 16.00 48.7 16.22 48.7 16.58 48.5 16.93 48.4 17.56
-13.7 -15.0 50.0 15.48
49.8 16.04 49.7 16.26 49.6 16.66 49.4 16.91 49.2 17.55
-11.8 -13.0 50.8 15.56 50.7 16.02 50.5 16.26 50.6 16.59 50.2 16.20 50.2 17.43
-9.8 -11.0 51.8 15.55 51.6 16.03 51.5 16.19 51.4 16.48 51.1 16.73 51.0 17.20
-9.5 -10.0 52.2 15.51 52.1 16.00 51.9 16.12 52.0 16.48 51.5 16.62 51.4 17.16
-8.5 -9.1 52.6 15.49 52.4 15.88 52.3 16.07 52.3 16.33 51.9 16.57 51.8 17.01
-7.0 -7.6 53.1 15.39 53.0 15.78 52.8 15.92 52.9 16.21 52.5 16.36 52.5 16.88
-5.0 -5.6 55.1 15.54 54.9 15.92 54.9 16.05 54.7 16.31 54.7 16.54 54.7 17.00
-3.0 -3.7 57.7 15.89 57.7 16.25 57.5 16.37 57.5 16.60 57.5 16.84 55.1 16.19
0.0 -0.7 62.3 16.41 62.3 16.74 62.1 16.83 61.1 16.61 59.1 15.98 55.1 14.72
3.0 2.2 67.3 16.87 67.1 17.17 63.1 15.68 61.1 15.11 59.1 14.56 55.1 13.40
5.0 4.1 70.7 17.18 67.1 16.13 63.0 14.73 61.1 14.24 59.1 13.71 55.1 12.65
7.0 6.0 71.1 16.30 67.1 15.17 63.0 13.10 61.1 13.41 59.1 12.92 55.1 11.92
9.0 7.9 72.7 15.66 67.8 14.42 63.0 12.98 61.1 12.64 59.1 12.18 55.1 11.25
11.0 9.8 72.7 14.75 67.8 13.59 63.0 12.26 61.1 11.92 59.1 11.50 55.1 10.63
13.0 11.8 72.7 13.85 67.8 12.78 63.0 11.56
61.1 11.24 59.1 10.85 55.1 10.04
15.0 13.7 72.7 13.06 67.8 12.06 63.0 10.92 61.1 10.63 59.1 10.25 55.1 9.51
18.0 16.8 72.7 12.32 67.8 11.51 63.0 10.57 61.1 10.09 59.1 9.71 55.1 9.06
20.0 18.5 72.7 11.63 67.8 11.04 63.0 10.14 61.1 9.64 59.1 9.26 55.1 8.69
24.0 20.5 72.7 10.99 67.8 10.67 63.0 9.75 61.1 9.28 59.1 8.90 55.1 8.42
GMV6 DC Inverter VRF Units Technical Sales Guide
89