Combination
Outdoor air
temp
Indoor air temperature ℃ DB
16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
℃ DB ℃ WB kW kW kW kW kW kW kW kW kW kW kW kW
120%
-19.8 -20.0 48.3 15.75 48.3 16.73 48.1 17.41 48.1 17.90 48.0 18.41 47.9 19.46
-18.8 -19.0 48.8 15.95 48.6 16.90 48.5 17.28 48.4 18.02 48.4 18.53 48.3 19.59
-16.7 -17.0 49.5 16.21 49.4 17.10 49.3 17.63 49.3 18.18 49.2 18.66 49.1 19.60
-13.7 -15.0 50.5 16.47 50.4 17.32 50.2 17.85 50.2 18.31 50.1 18.76 50.0 19.65
-11.8 -13.0 51.4 16.73 51.3 17.47 51.2 17.95 51.1 18.37 51.1 18.86 50.9 19.63
-9.8 -11.0 53.3 17.22 53.1 17.92 53.1 18.34 52.9 18.76 52.9 19.16 52.7 19.97
-9.5 -10.0 54.6 17.53 54.4 18.23 54.2 18.61 54.2 19.03 54.2 19.28 54.0 20.19
-8.5 -9.1 55.7 17.80 55.5 18.47 55.5 18.85 55.3 19.24 55.3 19.67 55.1 20.41
-7.0 -7.6 57.7 18.26 57.7 18.91 57.5 19.26 57.5 19.66 57.3 20.03 57.3 20.75
-5.0 -5.6 60.8 18.84 60.6 19.47 60.3 19.79 60.3 20.16 60.3 20.54 60.1 21.21
-3.0 -3.7 63.6 19.40 63.6 20.00 63.4 20.28 63.4 20.63 63.2 21.00 63.2 21.65
0.0
-0.7 68.7 20.23 68.7 20.78 68.4 21.27 68.4 21.36 68.2 21.69 68.2 22.31
3.0 2.2 74.7 21.14 74.5 21.65 73.9 21.69 73.7 22.02 73.7 22.32 72.2 22.27
5.0 4.1 78.6 21.65 78.4 22.14 77.6 22.11 77.4 22.41 77.4 22.71 72.2 20.92
7.0 6.0 82.5 22.07 81.9 22.36 81.6 22.50 80.2 22.22 77.6 21.40 72.2 19.69
9.0 7.9 86.5 22.46 85.8 22.76 83.4 21.85 80.2 20.91 77.6 20.13 72.2 18.54
11.0 9.8 90.5 22.74 88.2 22.32 83.4 20.56 80.2 19.69 77.6 18.95 72.2 17.47
13.0 11.8 93.7 22.50 88.2 20.94 83.4 19.29 80.2 18.50 77.6 17.82 72.2 16.44
15.0 13.7 93.7 21.19 88.2 19.72 83.4 18.22 80.2 17.44 77.6 16.81 72.2 15.52
18.0 16.8 93.7 20.02 88.2 18.67 83.4 17.30 80.2 16.54 77.6 15.93 72.2 14.72
20.0 18.5 93.7 18.97 88.2 17.82 83.4 16.56 80.2 15.77 77.6 15.18 72.2 14.02
24.0 20.5 93.7 18.05 88.2 17.09 83.4 15.96 80.2 15.12 77.6 14.58 72.2 13.44
110%
-19.8 -20.0 48.2 17.17 48.0 18.02 48.0 18.62 47.9 19.09 47.9 19.56 47.8 20.58
-18.8 -19.0 48.6 17.32 48.5 18.10 48.3 18.63 48.4 19.13 48.3 19.69 48.2 20.53
-16.7 -17.0 49.4 17.50 49.2 18.32 49.2 18.75 49.1 19.27 49.1 19.72 49.0 20.64
-13.7 -15.0 50.3 17.67
50.2 18.48 50.1 18.90 50.0 19.32 50.0 19.74 49.9 20.61
-11.8 -13.0 51.2 17.88 51.1 18.51 51.0 18.92 51.0 19.31 50.9 19.78 50.9 20.54
-9.8 -11.0 53.1 18.26 52.9 18.91 52.9 19.23 52.7 19.63 52.7 20.02 52.7 20.74
-9.5 -10.0 54.4 18.55 54.2 19.18 54.0 19.50 54.0 19.88 54.0 20.26 53.8 20.96
-8.5 -9.1 55.5 18.80 55.3 19.42 55.3 19.72 55.3 20.10 55.1 20.48 55.1 21.16
-7.0 -7.6 57.5 19.23 57.5 19.81 57.3 20.08 57.3 20.46 57.9 20.82 57.1 21.50
-5.0 -5.6 60.6 19.77 60.3 20.35 60.1 20.57 60.1 20.92 63.0 21.29 59.9 21.93
-3.0 -3.7 63.4 20.28 63.4 20.81 63.2 21.03 63.2 21.36 68.2 21.71 63.0 22.32
0.0 -0.7 68.4 21.03 68.4 21.54 68.2 21.71 68.2 22.02 71.1 22.36 66.3 21.99
3.0 2.2 74.8 21.99 74.2 22.34 74.0 22.42 73.8 22.71 71.1 21.77 66.3 20.02
5.0 4.1 78.5 22.39 78.2 22.77 76.4 22.15 73.5 21.26 71.1 20.47 66.3 18.84
7.0 6.0 82.2 22.73 81.6 22.89 76.4 20.84 73.6 20.02 71.1 19.25 66.3 17.73
9.0 7.9 86.3 23.07 81.6 21.52 76.5 19.65 73.7 18.87 71.1 18.13 66.3 16.72
11.0 9.8 86.3 21.70 81.6 20.24 76.5 18.50 73.7 17.79 71.1 17.09 66.3 15.78
13.0 11.8 86.3 20.36 81.6 18.99 76.5 17.40
73.7 16.74 71.1 16.09 66.3 14.86
15.0 13.7 86.3 19.18 81.6 17.91 76.5 16.44 73.7 15.80 71.1 15.22 66.3 14.07
18.0 16.8 86.3 18.15 81.6 16.98 76.5 15.00 73.7 14.99 71.1 14.50 66.3 13.39
20.0 18.5 86.3 17.22 81.6 16.15 76.5 14.24 73.7 14.27 71.1 13.90 66.3 12.81
24.0 20.5 86.3 16.44 81.6 15.41 76.5 13.56 73.7 13.67 71.1 13.39 66.3 12.33
GMV6 DC Inverter VRF Units Technical Sales Guide
93