EasyManua.ls Logo

Bircher Reglomat ProLoop 2 - Basic Functions; Time Functions; Sensitivity Adjustment; Automatic Sensitivity Boost (ASB)

Bircher Reglomat ProLoop 2
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Relay response to malfunctions (see chapter 6 Troubleshooting):
The relay picks up when the
loop is activated and drops
out when the loop is exited.
Loop
Relay
On delay:
The relay picks up after the
time t when the loop is acti-
vated and drops out when
the loop is exited.
Loop
Relay
t
t
Off delay:
The relay picks up when the
loop is activated and drops
out after the time t when the
loop is exited.
Loop
Relay
tt
Activation pulse:
The relay picks up when the
loop is activated and drops
out again after the time t.
Loop
Relay
tt
Impulse by leaving the loop:
By leaving the loop,
the relay picks up after
the time t, relay drops out.
Loop
Relay
tt
Max. presence:
he relay picks up when the
loop is activated and drops
out again after leaving, but
at least after the time t.
Loop
Relay
tt
1.Door/gate
systems
A malfunction causes
the output relay to be
released. The alarm
relay drops out.
2. Barrier
A malfunction causes
the output relay to pick
up. The alarm relay
drops out.
3. Quiescent
current
A malfunction causes
the output relay to be
released. The alarm
relay drops out.
4. Direction logic
(2-loop device
only)
A malfunction causes
the output relays to be
released. The alarm
relay drops out.
*factory settings
Note: The set parameter values are retained after a power failure, independent from the “Protection against power failure” function.
P 1 = Protection against power failure activated: The sensitivity is restricted to 1–5.
Time functions 1 , time unit 2 and time factor 3 (Einstellungen siehe Tabelle 4.11a)
4.3
Parameters
1: Door and gate The assigned output relay picks up when the loop is activated and drops out when the loop returns to a non-activated condition.
2: Barrier The assigned output relay picks up when the loop is activated and drops out when the loop returns to a non-activated condition.
3
: Quiescent current The assigned output relay drops out when the loop is activated and picks up again when the loop returns to a non-activated condition.
4: Direction logic Output 1 switches if an object moves from loop 1 to 2. Output 2 switches if an object moves from loop 2 to 1. Both loops must be
activated for a short time. The outputs are reset again when loop 2 returns to a non-activated condition. Both loops must have re-
turned to a non-activated condition for another direction detection.
0: Loop 2 Loop 2 can be deactivated in a 2-loop device.
Basic functions 0 (see Table 4.11a for settings)
4.2
Signal characteristics with protection against power failure active (Function 9 = 1)
4 .9.1
For Activation (e.g. Barriers)
Basic function 0 = 2 Barrier systems
Without power Initialisation Free Occupied Free
For Safeguarding (e.g. Barriers, bollards)
Basic function 0 = 3 Quiescent current
Without power Initialisation Free Occupied Free
open (no)
closed (nc)
open (no)
closed (nc)
Output
Output
The sensitivity 5 (=Sensitivity) of the loop detector can be adapted in 9 stages: 51 = Lowest sensitivity, 59 = Highest sensitivity,
54 = Factory setting.
In a device with 2 outputs, output 2 can be either activated or deactivated. In ProLoop 11, output 2 can also be set as an alarm output.
Four different frequencies F1, F2, F3, F4* can be set in order to avoid interference when using several loop detectors.
The direction logic function can only be used with a 2-loop device. Direction logic must have been set in the basic function (see chapter 4.2). Detection
can be performed from: Loop 1 to loop 2 From loop 2 to loop 1 from both directions
ASB (=Automatic Sensitivity Boost). ASB is required in order to be able to recognise trailer drawbars after activation.
Sensitivity 4 (see Table 4.11a for settings)
4.4
Automatic Sensitivity Boost ASB 5 (see Table 4.11a for settings)
4.5
Frequency 6 (see Table 4.11a for settings)
4.6
Direction logic7 (see Table 4.11a for settings)
4.7
Output 2 8 (see Table 4.11b for settings)
4.8
Protection against power failure 9 (see Table 4.11a for settings)
4.9
Display after start-up:
1
Touch the «Mode» button once
to change to configuration
mode
Mode
Sim1
1
Display after start-up:
1
2
Touch the «Mode» button once
to change to configuration
mode
Mode
Sim1
1
Mode
Sim1
2
Loop 2 is
selected
Loop 1 is
selected
1- loop device
2- loop device
Changeover from operation to configuration mode
4.10

Related product manuals